FCRG composite capacitive wall bushing gradually reduces the high voltage through the principle of capacitive voltage division, and the capacitive terminal lead wire is drawn from the flange, and connected with the grounding bolt. So that the high voltage lead wire safely through the wall or floor, etc., It plays the role of insulation and support diversion equipment.
Structure
FCRG composite capacitive wall bushing is composed of the primary winding, housing, current carrier contactor, capacitor core, silicone rubber sheds, flange, and contactor clamps. The main insulation inside is divided into composite film capacitive insulation and rubber-impregnated fiber capacitive insulation. The main insulation outside is divided into high-temperature vulcanized composite rubber and porcelain. which can meet the needs of different users. There is a measuring tap on the flange. When partial discharge and dielectric loss factors are measured, it is turned on and used. It should be reliably grounded during normal operation. The two ends of the product are the cable clamps.
Features
on-gas, no oil
· Fireproof, explosion proof
· Maintenance-free
· Smaller volume, lighter weight
Parameters
Standard: IEC 60137 Insulated bushing for alternating voltages above 1000V, GB/ ANSI/AS/EN/DIN/ IEC/ IEEE/ GOST
Rated voltage?12~550kV
Rated current?100~5000A
Rated frequency?50Hz?60Hz
Ambient air temperature?-40~+50?
Altitude?1000m?conferring with consumer if above 1000m?
Pollution class? ?????
Installation: indoor-indoor, outdoor-indoor, outdoor-outdoor, horizontal or vertical installation.
Highest voltage Um(kV) | Rated insulation level | Partial discharge level | ||
---|---|---|---|---|
Power frequency withstand voltage (kV) | Lightning impulse withstand voltage (kV) | Partial discharge test voltage (kV) | Partial discharge(pC) | |
12 | 42 | 75 | 12/7.3 | 10/5 |
24 | 50 | 125 | 24/15 | 10/5 |
40.5 | 95 | 200 | 40.5/25 | 10/5 |
52 | 95 | 250 | 52/32 | 10/5 |
72.5 | 140 | 350 | 72.5/44 | 10/5 |
126 (123) | 230 | 550 | 126/77 | 10/5 |
145 | 275 | 650 | 145/188 | 10/5 |
252 (245) | 460 | 1050 | 252/153 | 10/5 |
Dielectric loss factor is not greater than 0.005 under 10kV and 1.05Um/√3 (ambient air temperature 10~40?).
The highest temperature rising of winding is not greater than 75K.
Rated short-time thermal current is twenty-five times the rated current when time keeps up 1 second.
Minimum values of cantilever withstand load
Highest voltage Um (kV) | Rated current ?A? | |||
---|---|---|---|---|
≥800 | 1000~1600 | 2000~2500 | ≥3150 | |
12 | 1000 | 1250 | 2000 | 3150 |
24 | 1000 | 1250 | 2000 | 3150 |
40.5 | 1000 | 1250 | 2000 | 3150 |
52 | 1000 | 1250 | 2000 | 3150 |
72.5 | 1000 | 1250 | 2000 | 4000 |
126(123) | 1250 | 1600 | 2500 | 4000 |
145 | 1250 | 1600 | 2500 | 4000 |
252(245) | 1250 | 1600 | 2500 | 4000 |