Выбрать страницу

Composite capacitive wall bushing with CT

Standard: IEC60137, GB/T4109.
Rated voltage:12kV-0.5kV
Rated current:10A-8000A
Temperature:  -50 ℃ to +55℃
Altitude: 1000m(conferring with consumer if above 1000m)
Pollution class:Ⅲ for indoor, Ⅳ for outdoor.

drawing-of-separated-wall-bushing-with-CT

integrated wall bushing with CT

Parameters

Standard: IEC60137, GB/T4109.
Rated voltage:12kV-0.5kV
Rated current:10A-8000A
Temperature:  -50 ℃ to +55℃
Altitude: 1000m(conferring with consumer if above 1000m)
Pollution class:Ⅲ for indoor, Ⅳ for outdoor.

Highest voltage (Um) (kV) Rated Voltage (Ur) (kV) Power frequency withstand voltage (kV) BIL(kV) pC Tanδ (%) Ith(kA)
dry wet
12 10 28 28 75 ≤5 ≤0.3 25Ir
24 20 50 50 125 ≤5 ≤0.3 25Ir
40.5 35 95 80 200 ≤5 ≤0.3 25Ir
72.5 66 160(140) 140 350(325) ≤5 ≤0.3 25Ir
126 110 230(185) 230(185) 550(450) ≤5 ≤0.3 25Ir
252 220 460(395) 460(395) 1050(950) ≤5 ≤0.3 25Ir

 

Current value and bending failure load,

Installation

There are two installation methods for bushings on walls or tank shells: forward installation and reverse installation. The copper conductor wall bushing has both methods, which often easily make mistakes during operation, resulting in a shortened discharge distance and affecting bushing performance. The aluminum conductor and busbar wall bushing have unified reverse installation, which effectively utilizes the height of the porcelain bushing and reduces the size of the bushing.

40.5kV-wall-bushing-with-CT-integrated-2

126kV capacitive bushing with CT outdoor

126kV wall bushing with CT integrated

 

Leave Your Message